www.rinnai.us • © 2009 Rinnai America Corporation Condensing Boiler RS100 Controller Training Program Training Program #501102A – 062311
www.rinnai.us • © 2009 Rinnai America Corporation 10 RS100 Power-on Initialization The following sequence will occur every time power is reset or th
www.rinnai.us • © 2009 Rinnai America Corporation 11 THR 26MAR ’09 8:05 69º After entering a chapter or display, any setti
www.rinnai.us • © 2009 Rinnai America Corporation 12 RS100 Display Overview RS100 – Normal Operation Display Day, Date, Month, Year (currently Monda
www.rinnai.us • © 2009 Rinnai America Corporation 13 RS100 Operational Modes This allows selection of unique operational modes-a cursor is displaye
www.rinnai.us • © 2009 Rinnai America Corporation 14 DHW only will operate based on the times and temperatures set in the ―Timeprograms‖ chapter. If
www.rinnai.us • © 2009 Rinnai America Corporation 15 RS100 User Buttons This button adjusts the relation of boiler temperature to outside temperatur
www.rinnai.us • © 2009 Rinnai America Corporation 16 • Outside—displays current outside temperature reading from the outdoor reset sensor • Pressing
www.rinnai.us • © 2009 Rinnai America Corporation 17 Daytime room temperature setting Nighttime room temperature setting DHW temperature setting Aft
www.rinnai.us • © 2009 Rinnai America Corporation 18 Operational mode is changed to Party. A value will be displayed and available to change if need
www.rinnai.us • © 2009 Rinnai America Corporation 19 USER AND INSTALLER SETTINGS THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER
www.rinnai.us • © 2009 Rinnai America Corporation 2 Features and Benefits • Direct communication with the boiler allows it to fire based on the area
www.rinnai.us • © 2009 Rinnai America Corporation 20 Parameter Access There are two levels of access for making parameter changes: • The user level
www.rinnai.us • © 2009 Rinnai America Corporation 21 Parameter Chapters Once in the parameter menu, there are eight chapters that allow specific adj
www.rinnai.us • © 2009 Rinnai America Corporation 22 • Up to three events per day can be selected with a unique temperature (in Farhenheit or Celsiu
www.rinnai.us • © 2009 Rinnai America Corporation 23 Time Programs-Copy Feature • After setting one day’s time events, they can be copied in several
www.rinnai.us • © 2009 Rinnai America Corporation 24 Hydraulic Parameters • Hydraulic parameters should very rarely be adjusted • Hydraulic paramete
www.rinnai.us • © 2009 Rinnai America Corporation 25 System Parameters • Some System parameters are accessible but should never be adjusted. This is
www.rinnai.us • © 2009 Rinnai America Corporation 26 System Parameters (continued) PARA Description Range / Explanation Factory Setting User Access
www.rinnai.us • © 2009 Rinnai America Corporation 27 System Parameters (continued) PARA Description Range / Explanation Factory Setting User Access
www.rinnai.us • © 2009 Rinnai America Corporation 28 • Some DHW parameters are accessible but should never be adjusted. This is indicated with N/A a
www.rinnai.us • © 2009 Rinnai America Corporation 29 Unmixed (HC) Circuit Parameters • Some HC parameters are accessible but should never be adjuste
www.rinnai.us • © 2009 Rinnai America Corporation 3 Applications for the RS100 Room controller The RS100 is a room controller and not an on/off room
www.rinnai.us • © 2009 Rinnai America Corporation 30 PARA Description Range / Explanation Factory Setting User Access 3 Controller application type
www.rinnai.us • © 2009 Rinnai America Corporation 31 PARA Description Range / Explanation Factory Setting User Access 6 Inrush optimization OFF Not
www.rinnai.us • © 2009 Rinnai America Corporation 32 PARA Description Range / Explanation Factory Setting User Access 12 Min. temp limit 50°F to max
www.rinnai.us • © 2009 Rinnai America Corporation 33 Alarm Messages • The last 5 alarm messages can be viewed in the Alarm chapter. • The alarm numb
www.rinnai.us • © 2009 Rinnai America Corporation 34 Sensor Adjustment Chapter • Sensor adjustment allows an offset or calibration value to be appli
www.rinnai.us • © 2009 Rinnai America Corporation 35 Time Adjustment Chapter • Time adjustment allows date, day, and time for the RS100 • This is ac
www.rinnai.us • © 2009 Rinnai America Corporation 36 BOILER PARAMETER SETTINGS THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER’S INSTALLATION
www.rinnai.us • © 2009 Rinnai America Corporation 37 Boiler Parameters (in relation to the RS100) Parameter Chapter PARA Default Range Description
www.rinnai.us • © 2009 Rinnai America Corporation 38 Boiler Parameters (in relation to the RS100) Parameter Chapter PARA Default Range Description
www.rinnai.us • © 2009 Rinnai America Corporation 39 TROUBLESHOOTING THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLATIO
www.rinnai.us • © 2009 Rinnai America Corporation 4 Scope of Use- Single Zone System (RC mode) The RS100 can be used to control a single heating zon
www.rinnai.us • © 2009 Rinnai America Corporation 40 Troubleshooting • When troubleshooting with an RS100, consider the following: • Jumping the the
www.rinnai.us • © 2009 Rinnai America Corporation 41 Thank You for being a part of Rinnai’s Product Expansion – RS100 Boiler Controller Trai
www.rinnai.us • © 2009 Rinnai America Corporation 5 Scope of Use- Multiple Zone System (Outdoor Reset mode) Zone Thermostats Third Party Controller
www.rinnai.us • © 2009 Rinnai America Corporation 6 Zone Thermostats Third Party Controller Outdoor Sensor Zone Pump Piping The boiler in this appli
www.rinnai.us • © 2009 Rinnai America Corporation 7 INSTALLATION BASICS THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLA
www.rinnai.us • © 2009 Rinnai America Corporation 8 Electrical Connections Below is the connection for the RS100. Please refer to the installation m
www.rinnai.us • © 2009 Rinnai America Corporation 9 BASIC OPERATION THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLATIO